Ship fire damper FEX

ship fire damper
ship fire damper
Add to favorites
Compare this product
 

Characteristics

Options
for ships

Description

The Halton FEX fire dampers are type-approved class H0(H120) fire dampers for use in offshore, nuclear and navy ventilation systems. FEX dampers are used to protect the integrity of bulkheads where they are penetrated by ventilation ducts. The Halton FEX dampers can be installed in rectangular or circular ducts. Dampers have a fusible link and they prevent the spread of fire and gases within the ventilation ductwork. When the blades are in a open position, the device does not cause significant pressure loss, noise or flow disturbance. FEX dampers are set from outside and are suitable to be installed in bulkheads. An open-closed label is visible on the outside of the damper. Type approved by most recognized classification societies, class H0(H120) fire damper when suitably insulated Available as ATEX approved Fixed frame and blades of stainless steel Painted frame surface as an option on request Blades contain thermal expansion seals Nominal fuse release temperature 50 ºC, 74 ºC or 100 ºC. Other temperatures available. Automatic electrical, pneumatic or spring operation system available Maximum duct pressure for damper construction 5000 Pa and maximum air velocity 15 m/s
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.